{"id":1644,"date":"2026-10-27T13:24:48","date_gmt":"2026-10-27T05:24:48","guid":{"rendered":"https:\/\/brt-testing.com\/?p=1644"},"modified":"2026-10-27T13:24:48","modified_gmt":"2026-10-27T05:24:48","slug":"fire-testing-methods-for-electrical-enclosures","status":"publish","type":"post","link":"https:\/\/brt-testing.com\/de\/fire-testing-methods-for-electrical-enclosures\/","title":{"rendered":"Fire Testing Methods for Electrical Enclosures"},"content":{"rendered":"<h2>The Short Answer<\/h2>\n<p><strong>Electrical enclosure fire testing is not one test \u2014 it is a matrix, and the row is decided by the ignition scenario you are protecting against.<\/strong> Four scenarios cover almost every enclosure question. A small flame from outside is answered by the 50 W horizontal and vertical flame test in IEC 60695-11-10, which produces the familiar HB and V-0, V-1, V-2 classifications <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2938\" target=\"_blank\" rel=\"noopener\">1<\/a>. A larger flame is answered by the 500 W method in IEC 60695-11-20, which adds a plaque burn-through check and yields 5VB and 5VA <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2944\" target=\"_blank\" rel=\"noopener\">2<\/a>. An overheated internal connection is answered by the glow-wire family \u2014 IEC 60695-2-11 for finished parts, IEC 60695-2-12 for the material flammability index and IEC 60695-2-13 for the ignition temperature <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2951\" target=\"_blank\" rel=\"noopener\">4<\/a><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2952\" target=\"_blank\" rel=\"noopener\">5<\/a><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/62845\" target=\"_blank\" rel=\"noopener\">6<\/a><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/62846\" target=\"_blank\" rel=\"noopener\">7<\/a>. A small flame from a fault condition inside the equipment is answered by the needle-flame test in IEC 60695-11-5 <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/27371\" target=\"_blank\" rel=\"noopener\">3<\/a>. Start from the end-product standard, not from the material datasheet: the product standard names the test, the severity and the specimen, and the material rating is only evidence submitted into that test.<\/p>\n<figure style=\"margin:24px 0\">\n  <a href=\"https:\/\/brt-testing.com\/product\/horizontal-vertical-combustion-tester\/\"><img decoding=\"async\" src=\"https:\/\/brt-testing.com\/wp-content\/uploads\/2026\/09\/Horizontal-Vertical-Combustion-Tester.jpg\" alt=\"Horizontal and vertical combustion tester configured for IEC 60695-11-10 and IEC 60695-11-20 small-flame testing of enclosure materials\" width=\"1000\" height=\"1000\" style=\"width:100%;height:auto\" loading=\"lazy\"><\/a><figcaption style=\"font-size:13px;color:#666;margin-top:6px\">A small-flame chamber covers the 50 W and 500 W methods with a change of burner and specimen holder. It is the first building block of any electrical enclosure fire testing capability.<\/figcaption><\/figure>\n<h2>What Electrical Enclosure Fire Testing Actually Covers<\/h2>\n<p>The reason enclosure testing feels complicated is that a single enclosure can be asked to resist four physically different events, and no one test models more than one of them.<\/p>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:18.65%\">\n<col style=\"width:24.02%\">\n<col style=\"width:18.65%\">\n<col style=\"width:20.73%\">\n<col style=\"width:17.96%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Ignition scenario<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">What it simulates<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Method<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Standard<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">What comes out<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Small external flame<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A nearby fire or a discarded match<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">50 W horizontal and vertical flame<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-11-10 [1]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">HB, or V-0 \/ V-1 \/ V-2<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Large external flame<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A developed fire against a barrier<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">500 W vertical flame<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-11-20 [2]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">5VB, 5VA<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Overheated internal connection<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A glowing or hot wire inside the equipment<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Glow-wire<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-2-11 \/ 2-12 \/ 2-13 [5][6][7]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Pass at temperature, GWFI, GWIT<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Small flame from a fault<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">An arc or a failing component<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Needle flame<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-11-5 [3]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Pass or fail<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>Notice the split in the third column. Two of the four are <strong>material tests<\/strong> \u2014 they are run on standard bar or plaque specimens and produce a classification the material carries. The other two are <strong>finished-part tests<\/strong> \u2014 they are run on the enclosure itself, mounted in its normal position, and produce a pass or fail at a stated temperature or application time. Confusing the two is the single most common reason an enclosure submission comes back from a certifier.<\/p>\n<h2>Material-Level Flame Tests<\/h2>\n<h3>The 50 W horizontal and vertical flame test<\/h3>\n<p>IEC 60695-11-10:2013 specifies small-scale laboratory procedures that compare the burning behaviour of materials used in electrotechnical products when vertically or horizontally oriented bar specimens are exposed to a small flame ignition source with a nominal thermal power of 50 W [1]. Two methods are published. <strong>Method A<\/strong> is the horizontal burning test and determines the linear burning rate. <strong>Method B<\/strong> is the vertical burning test and determines whether a material self-extinguishes. The scope is explicit about what is excluded: the methods apply to solid and cellular materials with an apparent density of more than 250 kg\/m\u00b3 determined in accordance with ISO 845, so a low-density foam does not belong in this test [1]. The edition currently listed by IEC is 2.0, published 2013-05-21, with a stability date of 2028 [1].<\/p>\n<p>In the UL system the same 50 W experiment produces the V-0, V-1 and V-2 classifications, and we set the criteria out in <a href=\"https:\/\/brt-testing.com\/ul-94-flammability-testing-hb-v-0-v-1-and-v-2-explained\/\">our guide to UL 94 HB, V-0, V-1 and V-2<\/a>. The flame itself is a calibrated artefact: IEC publishes the 50 W flame specification and its confirming test separately as IEC 60695-11-3 <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2946\" target=\"_blank\" rel=\"noopener\">8<\/a>.<\/p>\n<h3>The 500 W flame test<\/h3>\n<p>Where an enclosure wall has to keep acting as a barrier rather than merely stop burning, the 500 W method applies. IEC 60695-11-20 is the IEC publication of that method, with the current consolidated text being the 1999 edition together with amendment 1 of 2003 [2], and the 500 W flame itself is specified with its confirming test in IEC 60695-11-4 <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2948\" target=\"_blank\" rel=\"noopener\">9<\/a>. The practical difference from the 50 W test is the addition of plaque specimens judged on burn-through, which is what separates 5VA from 5VB. We cover the whole 500 W series in <a href=\"https:\/\/brt-testing.com\/ul-94-5v-testing-what-makes-it-different\/\">UL 94 5V testing: what makes it different<\/a>.<\/p>\n<h3>Oxygen index as a formulation screen<\/h3>\n<p>Neither flame test is a good tool for ranking candidate formulations, because both return a classification rather than a number. ISO 4589-2 returns a number \u2014 the minimum oxygen concentration that supports candle-like combustion \u2014 which makes it far more sensitive to small formulation changes <a href=\"https:\/\/webstore.uni.com\/en\/iso-4589-2-2017\" target=\"_blank\" rel=\"noopener\">10<\/a>. Use it upstream: screen three or four candidates, then submit the winner to the conditioned flame tests rather than paying for five full submissions.<\/p>\n<h2>Finished-Part Tests<\/h2>\n<p>Electrical enclosure fire testing splits cleanly at this point: two of the four scenarios are material tests and two are finished-part tests, and the second pair is the one that catches design problems.<\/p>\n<h3>Glow-wire flammability: GWEPT and GWFI<\/h3>\n<p>The glow-wire family simulates thermal stress from an electrically heated source. IEC 60695-2-10:2013 is the apparatus and common test procedure; the three application standards that sit on top of it are deliberately separated by what is being tested [4].<\/p>\n<p><strong>GWEPT<\/strong>, the glow-wire flammability test for end products in IEC 60695-2-11:2014, is run on the finished article. Its stated purpose is to simulate the effects of thermal stresses produced by an electrically heated source, and to check that an end product exposed to that source has either a limited ability to ignite or, if it ignites, a limited ability to propagate flame [5]. This is the test that catches a design problem no material test can find \u2014 a rib, a boss or a wall thickness that concentrates heat in one place.<\/p>\n<p><strong>GWFI<\/strong>, the glow-wire flammability index in IEC 60695-2-12:2021, is a materials test. IEC defines it precisely: GWFI is the highest temperature, determined during the standardised procedure, at which the material does not ignite, or if it does, extinguishes within 30 s after removal of the glow-wire and is not totally consumed, and molten drips, if they occur, do not ignite the wrapping tissue [6]. Note the form of the result \u2014 it is a temperature, not a pass or fail, which is exactly what a materials specifier needs.<\/p>\n<h3>Glow-wire ignition temperature: GWIT<\/h3>\n<p>IEC 60695-2-13:2021 is the companion materials test for ignitability, and its definition is worth quoting rather than paraphrasing. The glow-wire ignition temperature is the temperature which is 25 K (or 30 K) higher than the maximum test temperature, determined during the standardised procedure, at which the material does not ignite, or at which sustained flaming combustion does not occur for longer than 5 s for any single flame event and the specimen is not totally consumed [7]. The 25 K or 30 K margin is not a rounding convention \u2014 it is built into the definition, because the index is meant to be used as a design headroom figure rather than as a measured physical threshold.<\/p>\n<h3>The needle flame test<\/h3>\n<p>IEC 60695-11-5:2016 specifies a needle-flame test to simulate the effect of a small flame that may result from fault conditions, in order to assess fire hazard by a simulation technique [3]. It applies to electrotechnical equipment, its sub-assemblies and components, and to solid electrical insulating materials or other combustible materials. The second edition, published in 2016, cancels and replaces the first edition of 2004 [3] \u2014 worth checking, because a great deal of older test documentation still cites the 2004 edition. In use, a small calibrated flame is applied to the part, typically for a defined application time, and the part passes if it does not ignite or if flaming and glowing cease within the specified period and the tissue paper beneath is not ignited.<\/p>\n<figure style=\"margin:24px 0\">\n  <a href=\"https:\/\/brt-testing.com\/product\/bundled-cable-vertical-flame-test-equipment\/\"><img decoding=\"async\" src=\"https:\/\/brt-testing.com\/wp-content\/uploads\/2026\/09\/IEC60332-3-10-Bundled-Cable-Vertical-Flame-Test-Equipment.jpg\" alt=\"IEC 60332-3-10 bundled cable vertical flame test equipment with a vertical ladder and a calibrated ribbon burner in the test chamber\" width=\"1000\" height=\"1000\" style=\"width:100%;height:auto\" loading=\"lazy\"><\/a><figcaption style=\"font-size:13px;color:#666;margin-top:6px\">Where the enclosure is part of a cable or wiring system rather than a standalone box, the vertical flame propagation methods come into play alongside the enclosure tests.<\/figcaption><\/figure>\n<h2>Matching the Method to the Question<\/h2>\n<p>The point of electrical enclosure fire testing is to answer one question per scenario, and the table below is the shortest route from question to method.<\/p>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:38.89%\">\n<col style=\"width:26.99%\">\n<col style=\"width:34.12%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Question you are actually asking<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Run this<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Do not run this<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Will this grade self-extinguish?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-11-10 Method B [1]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Glow-wire \u2014 it answers a different ignition source<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Will this wall stay intact as a barrier?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-11-20 [2]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">The 50 W test \u2014 it never asks about burn-through<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Does this finished enclosure survive an overheated terminal?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-2-11 GWEPT [5]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A bar test \u2014 geometry is not represented<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">What temperature headroom does this grade have?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-2-12 GWFI [6] or 2-13 GWIT [7]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A single pass or fail at one temperature<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Does a fault-induced small flame propagate?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">IEC 60695-11-5 [3]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Anything run on a bar<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Which of four formulations should be submitted?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 4589-2 [10]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A full conditioned flame series on all four<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<h2>What the End-Product Standard Actually Asks For<\/h2>\n<p>This is the step that saves the most money, and it is the one most often skipped. Electrical enclosure fire testing is almost never self-directed: an assembly standard, a product family standard or a customer specification calls up the method, the severity and the specimen. Read that clause first and copy it into the test request verbatim.<\/p>\n<p>Three things in that clause do the damage when they are missed. The <strong>severity<\/strong> \u2014 a glow-wire temperature of 550 \u00b0C and one of 850 \u00b0C are different submissions, and a material that passes one may fail the other. The <strong>specimen<\/strong> \u2014 finished part or standard bar, and if a finished part, whether it is mounted in its end-use position. And the <strong>edition<\/strong> \u2014 IEC 60695-11-5 moved from 2004 to 2016 [3], and IEC 60695-2-12 and 2-13 both moved to 2021 editions [6][7], so a request quoting the old number may be tested to the wrong procedure.<\/p>\n<p>If your products sit under the IEC 60695 umbrella rather than a specific assembly standard, our <a href=\"https:\/\/brt-testing.com\/iec-60695-flammability-testing-a-practical-guide\/\">practical guide to IEC 60695 flammability testing<\/a> walks through the series part by part.<\/p>\n<h2>Setting Up an Electrical Enclosure Fire Testing Capability<\/h2>\n<p>A laboratory that wants to answer all four scenarios needs three instruments, not one, and they are bought in this order in most cases.<\/p>\n<p><strong>A small-flame chamber<\/strong> comes first, because it covers the two material classifications that almost every enclosure datasheet quotes. It needs both burner positions \u2014 a 50 W flame and a 500 W flame \u2014 plus bar clamps and a plaque holder. Our <a href=\"https:\/\/brt-testing.com\/product\/horizontal-vertical-combustion-tester\/\">horizontal and vertical combustion tester<\/a> is configured for exactly that pairing, and the <a href=\"https:\/\/brt-testing.com\/product\/plastic-foam-vertical-horizontal-burning-tester\/\">plastic foam vertical and horizontal burning tester<\/a> covers the cellular materials that IEC 60695-11-10 excludes by density [1].<\/p>\n<figure style=\"margin:24px 0\">\n  <a href=\"https:\/\/brt-testing.com\/product\/intelligent-automatic-touch-screen-oxygen-index-tester\/\"><img decoding=\"async\" src=\"https:\/\/brt-testing.com\/wp-content\/uploads\/2026\/09\/JYZS-10-Oxygen-Index-Tester.jpg\" alt=\"JYZS-10 intelligent automatic touch screen oxygen index tester used to screen enclosure formulations to ISO 4589-2\" width=\"1000\" height=\"1000\" style=\"width:100%;height:auto\" loading=\"lazy\"><\/a><figcaption style=\"font-size:13px;color:#666;margin-top:6px\">An oxygen index tester turns a pass-or-fail question into a number, which is what makes it the cheapest way to rank enclosure formulations before a conditioned submission.<\/figcaption><\/figure>\n<p><strong>An oxygen index tester<\/strong> comes second, and it is the one that changes how the laboratory works. Because ISO 4589-2 returns a continuous scale [10], formulation screening stops being a queue of four-week flame submissions. Both the <a href=\"https:\/\/brt-testing.com\/product\/intelligent-automatic-touch-screen-oxygen-index-tester\/\">automatic touch-screen oxygen index tester<\/a> and the <a href=\"https:\/\/brt-testing.com\/product\/plastic-loi-limiting-oxygen-index-tester\/\">limiting oxygen index tester for plastics<\/a> are built to that method.<\/p>\n<p><strong>A glow-wire apparatus<\/strong> comes third, and it is the only one of the three that tests the enclosure rather than the material. If the products in scope include cable and wiring systems, a <a href=\"https:\/\/brt-testing.com\/product\/cable-fire-resistance-tester\/\">cable fire resistance tester<\/a> and <a href=\"https:\/\/brt-testing.com\/product\/bundled-cable-vertical-flame-test-equipment\/\">bundled cable vertical flame test equipment<\/a> extend coverage into those methods; we cover the cable side in <a href=\"https:\/\/brt-testing.com\/iec-60331-cable-fire-resistance-test-explained\/\">IEC 60331 cable fire resistance testing<\/a>.<\/p>\n<h2>Mistakes That Delay an Enclosure Submission<\/h2>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:36.21%\">\n<col style=\"width:34.91%\">\n<col style=\"width:28.88%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Mistake<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Why it costs time<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">What to do instead<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Submitting a material classification as if it were a product approval<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Material tests and finished-part tests answer different questions<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Read the end-product clause and test what it names<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Running glow-wire at one temperature and reporting &#8220;glow-wire compliant&#8221;<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">The result is a temperature, not a pass<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Report GWFI and GWIT as temperatures [6][7]<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Testing foams to IEC 60695-11-10<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">The method excludes materials below 250 kg\/m\u00b3 apparent density [1]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Use the foam-specific procedure<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Quoting the 2004 edition of IEC 60695-11-5<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">It was cancelled and replaced by the 2016 edition [3]<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Check the edition in the current catalogue<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Screening formulations with flame tests<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">They return classes, not numbers<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Screen with ISO 4589-2 first [10]<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Assuming 5VA and V-0 are interchangeable<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">5VA adds a plaque burn-through requirement<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Specify the rating the standard calls up<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<h2>Frequently Asked Questions<\/h2>\n<h4>Which fire test does an electrical enclosure actually need?<\/h4>\n<p>It depends on the end-product standard, not on the material. Most enclosures need a small-flame material classification under IEC 60695-11-10 and a glow-wire test on the finished part under IEC 60695-2-11. If the enclosure wall has to act as a fire barrier, the 500 W method in IEC 60695-11-20 is added, and if internal faults are a concern, the needle-flame test in IEC 60695-11-5 applies.<\/p>\n<h4>Is a UL 94 V-0 rating enough to prove an enclosure is safe?<\/h4>\n<p>No. V-0 is a material classification from a 50 W flame test on a standard bar. It says nothing about how the finished enclosure behaves around an overheated terminal, which is what the glow-wire test on the end product is for, and nothing about burn-through, which is what the 500 W plaque test is for.<\/p>\n<h4>What is the difference between GWEPT and GWFI?<\/h4>\n<p>GWEPT, in IEC 60695-2-11, is run on a finished end product and gives a result for that product. GWFI, in IEC 60695-2-12, is run on standard material specimens and returns the highest temperature at which the material does not ignite or self-extinguishes within 30 s. One tests a design, the other grades a material.<\/p>\n<h4>How is GWIT different from GWFI?<\/h4>\n<p>GWFI is a flammability index: the highest temperature at which the material does not ignite, or ignites and extinguishes within 30 s of removing the glow-wire. GWIT is an ignitability index, defined as the temperature 25 K or 30 K above the highest test temperature at which the material did not ignite or did not sustain flaming for longer than 5 s.<\/p>\n<h4>Do I need both a bar test and a plaque test?<\/h4>\n<p>Only if you are claiming 5VA. The 50 W methods and the 5VB classification are decided on bars alone. Plaques of 150 mm by 150 mm are required for 5VA, because burn-through cannot be assessed on a bar.<\/p>\n<h4>Can I use one instrument for all the enclosure methods?<\/h4>\n<p>No. The flame tests, the glow-wire tests and the needle-flame test use different apparatus, and the flame test itself needs two burner configurations for the 50 W and 500 W methods. A practical capability is three instruments, and they are usually bought in that order.<\/p>\n<h4>Why does the edition of the standard matter so much here?<\/h4>\n<p>Because several parts of IEC 60695 have been revised recently. The needle-flame method moved from the 2004 edition to the 2016 edition, and the glow-wire materials tests moved to 2021 editions. A test request quoting an old edition may be run to a procedure the certifier no longer recognises.<\/p>\n<h2>The Decision Sequence<\/h2>\n<ol>\n<li><strong>Read the end-product clause and copy it verbatim into the test request.<\/strong> Method, severity, specimen and edition all come from there.<\/li>\n<li><strong>Classify the question as material or finished part.<\/strong> Material questions use IEC 60695-11-10, 11-20 and ISO 4589-2; finished-part questions use IEC 60695-2-11 and 11-5.<\/li>\n<li><strong>Screen formulations with ISO 4589-2 before spending money on conditioned flame submissions.<\/strong><\/li>\n<li><strong>Decide whether burn-through matters.<\/strong> If it does, ask for 5VA and commission plaques; if it does not, 5VB on bars is sufficient.<\/li>\n<li><strong>Report glow-wire results as temperatures<\/strong>, with the edition of the standard stated.<\/li>\n<li><strong>Check every edition against the current catalogue<\/strong> before the request goes out.<\/li>\n<\/ol>\n<p>If you are specifying a capability rather than a single instrument, <a href=\"https:\/\/brt-testing.com\/get-in-touch\/\">contact the BRT application team<\/a> with the standards your products are certified to, and we will map them to an instrument configuration. Our guide to <a href=\"https:\/\/brt-testing.com\/how-to-choose-a-fire-testing-laboratory-equipment-supplier\/\">choosing a fire testing laboratory equipment supplier<\/a> lists the questions worth putting to any vendor, and <a href=\"https:\/\/brt-testing.com\/how-to-test-the-flammability-of-plastic-materials\/\">how to test the flammability of plastic materials<\/a> covers the wider plastics picture.<\/p>\n<h2>About the Author<\/h2>\n<p>This article was prepared by the BRT combustion testing application team at Shenyang Baoruitong Automation Equipment Co., Ltd., which supplies small-flame chambers, oxygen index testers and cable and wiring fire test equipment to electrical and electronics laboratories. Standard scope statements are quoted from the publishers&#8217; own catalogue entries, and edition and date information is taken from the IEC webstore and ASTM International.<\/p>\n<h2>Sources<\/h2>\n<ol>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2938\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-11-10:2013, 50 W horizontal and vertical flame test methods<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2944\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-11-20:1999+AMD1:2003, 500 W flame test methods<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/27371\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-11-5:2016, needle-flame test method<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2951\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-2-10:2013, glow-wire apparatus and common test procedure<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2952\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-2-11:2014, glow-wire flammability test for end products (GWEPT)<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/62845\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-2-12:2021, glow-wire flammability index (GWFI) for materials<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/62846\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-2-13:2021, glow-wire ignition temperature (GWIT) for materials<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2946\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-11-3:2012, 50 W test flame apparatus and confirming test<\/a><\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/en\/publication\/2948\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60695-11-4:2011, 500 W test flame apparatus and confirming test<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/iso-4589-2-2017\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 ISO 4589-2:2017, oxygen index at ambient temperature<\/a><\/li>\n<li><a href=\"https:\/\/store.astm.org\/d3801-20a.html\" target=\"_blank\" rel=\"noopener\">ASTM International \u2014 D3801-20a, comparative burning characteristics of solid plastics in a vertical position<\/a><\/li>\n<\/ol>\n<hr \/>\n<p><!-- FAQ \/ Article JSON-LD --><br \/>\n<script type=\"application\/ld+json\">\n{\n \"@context\": \"https:\/\/schema.org\",\n \"@type\": \"FAQPage\",\n \"mainEntity\": [\n  {\n   \"@type\": \"Question\",\n   \"name\": \"Which fire test does an electrical enclosure actually need?\",\n   \"acceptedAnswer\": {\n    \"@type\": \"Answer\",\n    \"text\": \"It depends on the end-product standard, not on the material. Most enclosures need a small-flame material classification under IEC 60695-11-10 and a glow-wire test on the finished part under IEC 60695-2-11. If the enclosure wall has to act as a fire barrier, the 500 W method in IEC 60695-11-20 is added, and if internal faults are a concern, the needle-flame test in IEC 60695-11-5 applies.\"\n   }\n  },\n  {\n   \"@type\": \"Question\",\n   \"name\": \"Is a UL 94 V-0 rating enough to prove an enclosure is safe?\",\n   \"acceptedAnswer\": {\n    \"@type\": \"Answer\",\n    \"text\": \"No. V-0 is a material classification from a 50 W flame test on a standard bar. It says nothing about how the finished enclosure behaves around an overheated terminal, which is what the glow-wire test on the end product is for, and nothing about burn-through, which is what the 500 W plaque test is for.\"\n   }\n  },\n  {\n   \"@type\": \"Question\",\n   \"name\": \"What is the difference between GWEPT and GWFI?\",\n   \"acceptedAnswer\": {\n    \"@type\": \"Answer\",\n    \"text\": \"GWEPT, in IEC 60695-2-11, is run on a finished end product and gives a result for that product. GWFI, in IEC 60695-2-12, is run on standard material specimens and returns the highest temperature at which the material does not ignite or self-extinguishes within 30 s. One tests a design, the other grades a material.\"\n   }\n  },\n  {\n   \"@type\": \"Question\",\n   \"name\": \"How is GWIT different from GWFI?\",\n   \"acceptedAnswer\": {\n    \"@type\": \"Answer\",\n    \"text\": \"GWFI is a flammability index: the highest temperature at which the material does not ignite, or ignites and extinguishes within 30 s of removing the glow-wire. GWIT is an ignitability index, defined as the temperature 25 K or 30 K above the highest test temperature at which the material did not ignite or did not sustain flaming for longer than 5 s.\"\n   }\n  },\n  {\n   \"@type\": \"Question\",\n   \"name\": \"Do I need both a bar test and a plaque test?\",\n   \"acceptedAnswer\": {\n    \"@type\": \"Answer\",\n    \"text\": \"Only if you are claiming 5VA. The 50 W methods and the 5VB classification are decided on bars alone. Plaques of 150 mm by 150 mm are required for 5VA, because burn-through cannot be assessed on a bar.\"\n   }\n  },\n  {\n   \"@type\": \"Question\",\n   \"name\": \"Can I use one instrument for all the enclosure methods?\",\n   \"acceptedAnswer\": {\n    \"@type\": \"Answer\",\n    \"text\": \"No. The flame tests, the glow-wire tests and the needle-flame test use different apparatus, and the flame test itself needs two burner configurations for the 50 W and 500 W methods. A practical capability is three instruments, and they are usually bought in that order.\"\n   }\n  },\n  {\n   \"@type\": \"Question\",\n   \"name\": \"Why does the edition of the standard matter so much here?\",\n   \"acceptedAnswer\": {\n    \"@type\": \"Answer\",\n    \"text\": \"Because several parts of IEC 60695 have been revised recently. The needle-flame method moved from the 2004 edition to the 2016 edition, and the glow-wire materials tests moved to 2021 editions. A test request quoting an old edition may be run to a procedure the certifier no longer recognises.\"\n   }\n  }\n ]\n}\n<\/script><\/p>\n","protected":false},"excerpt":{"rendered":"<p>Electrical enclosure fire testing is a matrix, not a single test. A small external flame is answered by the 50 W method in IEC 60695-11-10; a large flame by the 500 W method in IEC 60695-11-20; an overheated internal connection by the glow-wire family in IEC 60695-2-11, 2-12 and 2-13; and a fault-induced small flame by the needle-flame method in IEC 60695-11-5. This guide sets out which method answers which question, quotes the GWFI and GWIT definitions from the IEC scope statements, and explains why the split between material tests and finished-part tests decides most enclosure submissions.<\/p>","protected":false},"author":1,"featured_media":1531,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[135],"tags":[],"class_list":["post-1644","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-interpretation-of-the-standard"],"_links":{"self":[{"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/posts\/1644","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/comments?post=1644"}],"version-history":[{"count":2,"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/posts\/1644\/revisions"}],"predecessor-version":[{"id":1651,"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/posts\/1644\/revisions\/1651"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/media\/1531"}],"wp:attachment":[{"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/media?parent=1644"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/categories?post=1644"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/brt-testing.com\/de\/wp-json\/wp\/v2\/tags?post=1644"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}