{"id":1616,"date":"2026-10-26T10:08:57","date_gmt":"2026-10-26T02:08:57","guid":{"rendered":"https:\/\/brt-testing.com\/?p=1616"},"modified":"2026-10-27T13:41:09","modified_gmt":"2026-10-27T05:41:09","slug":"iso-834-fire-resistance-testing-temperature-time-curve-explained","status":"publish","type":"post","link":"https:\/\/brt-testing.com\/it\/iso-834-fire-resistance-testing-temperature-time-curve-explained\/","title":{"rendered":"ISO 834 Fire Resistance Testing: Temperature-Time Curve Explained"},"content":{"rendered":"<h2>The Short Answer<\/h2>\n<p><strong>ISO 834 fire resistance testing exposes a building element to a single, standardised temperature-time curve and measures how long the element survives before it fails one of three criteria.<\/strong> The curve is a cellulosic (ordinary combustibles) fire curve, written as one equation:<\/p>\n<p><strong>T = 20 + 345 log\u2081\u2080(8t + 1)<\/strong><\/p>\n<p>where T is the average furnace temperature in degrees Celsius and t is the time in minutes from the start of the test <a href=\"https:\/\/webstore.uni.com\/en\/iso-834-1-2025\" target=\"_blank\" rel=\"noopener\">1<\/a>. The furnace is controlled so that its measured average temperature tracks that curve, and the element \u2014 a wall, a floor, a beam, a column or a door \u2014 is loaded and instrumented on one face while the other is exposed.<\/p>\n<p>The failure criteria are three, and they are independent: <strong>R<\/strong> for loadbearing capacity, <strong>E<\/strong> for integrity, and <strong>I<\/strong> for insulation. An element is rated to the number of minutes it holds all the criteria it is required to hold. The single most important practical point in 2026 is that the edition changed: ISO 834-1:1999 was withdrawn on 30 May 2025, and ISO 834-1:2025, published the same day, is the current edition [1]<a href=\"https:\/\/webstore.uni.com\/en\/iso-834-1-1999\" target=\"_blank\" rel=\"noopener\">2<\/a>. Any test plan still citing the 1999 edition should be corrected before it is signed off.<\/p>\n<h2>Where the Curve Comes From<\/h2>\n<h3>Why it is a convention rather than a physical law<\/h3>\n<p>The curve is not a physical law and it is not a measurement of any particular real fire. It is a convention, adopted so that two laboratories on different continents can produce comparable ratings for the same element. It rises steeply in the first minutes and then flattens, which is what a ventilation-controlled compartment fire was understood to do when the convention was set.<\/p>\n<p>Understanding that it is a convention matters for two reasons. First, it means a rating in minutes is not a prediction of how long the element survives in an arbitrary fire \u2014 it is a statement about performance under this specific thermal insult. Second, it means the curve&#8217;s realism can be argued about without invalidating its use, which is exactly why alternative curves exist for applications where a cellulosic fire is the wrong model.<\/p>\n<h3>What the curve is not<\/h3>\n<p>The most common misuse of the ISO 834 curve is to read it as an ordinary-compartment fire and then design around it. It is not that. It has no ventilation term, no fuel load term, no compartment geometry term, and no cooling phase \u2014 it rises monotonically and never decays. A real compartment fire grows, peaks and decays, and the decay phase is exactly where many assemblies either recover or finally fail.<\/p>\n<p>It is also not a hydrocarbon curve. Where the fire load is dominated by liquid or gaseous fuels \u2014 petrochemical, tunnel, or some marine and offshore applications \u2014 the temperature rise is faster and the specified curve is different. Choosing ISO 834 for those applications produces a rating that looks reassuring and models the wrong fire.<\/p>\n<figure style=\"margin:24px 0\">\n  <a href=\"https:\/\/brt-testing.com\/product\/vertical-integrated-fire-resistance-test-furnace\/\"><img decoding=\"async\" src=\"https:\/\/brt-testing.com\/wp-content\/uploads\/2026\/10\/fire-resistance-test.avif\" alt=\"Fire resistance test in progress with a wall specimen sealed into a vertical test furnace during ISO 834 fire resistance testing\" width=\"1536\" height=\"864\" style=\"width:100%;height:auto\" loading=\"lazy\"><\/a><figcaption style=\"font-size:13px;color:#666;margin-top:6px\">A wall specimen sealed into a vertical furnace during an ISO 834 fire resistance test. The exposed face follows the standard curve; the unexposed face is instrumented.<\/figcaption><\/figure>\n<h2>What the Curve Actually Produces<\/h2>\n<p>Substituting into the equation gives the values a furnace controller is chasing. These are computed from the equation, not quoted from a table:<\/p>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:21.7%\">\n<col style=\"width:14.62%\">\n<col style=\"width:25.49%\">\n<col style=\"width:38.19%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Time t (min)<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">8t + 1<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">log\u2081\u2080(8t + 1)<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Furnace temperature T (\u00b0C)<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">5<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">41<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1.6128<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">576<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">10<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">81<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1.9085<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">678<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">15<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">121<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">2.0828<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">738<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">30<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">241<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">2.3820<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">842<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">45<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">361<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">2.5575<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">902<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">60<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">481<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">2.6821<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">945<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">90<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">721<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">2.8579<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1,006<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">120<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">961<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">2.9827<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1,049<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">180<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1,441<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">3.1584<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1,110<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">240<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1,921<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">3.2835<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">1,153<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>Three things are worth reading out of that table. The curve gains about 270 \u00b0C in the first five minutes and only about 100 \u00b0C between two and four hours, so the severity is front-loaded. The 60-minute value of roughly 945 \u00b0C is the figure most people quote from memory, and it is the number to sanity-check a controller log against. And the increments get small enough that beyond about three hours the test is increasingly about the element&#8217;s slow thermal response rather than about rising severity.<\/p>\n<h3>ISO 834 and ASTM E119 are not the same curve<\/h3>\n<p>ASTM E119, <em>Standard Test Methods for Fire Tests of Building Construction and Materials<\/em> <a href=\"https:\/\/store.astm.org\/e0119-24.html\" target=\"_blank\" rel=\"noopener\">9<\/a>, specifies its furnace control as a <strong>tabulated<\/strong> set of temperature-time points rather than an equation. The two curves sit close together but are not identical, and the differences are largest in the first ten minutes. The practical consequence is that an &#8220;hour&#8221; under one standard is not interchangeable with an &#8220;hour&#8221; under the other, and a report has to name the standard it was run to.<\/p>\n<p>European practice reproduces the ISO 834 equation inside its own test method: EN 1363-1, <em>Fire resistance tests \u2014 Part 1: General requirements<\/em> <a href=\"https:\/\/webstore.uni.com\/en\/en-1363-1-2020\" target=\"_blank\" rel=\"noopener\">7<\/a>, is the general requirements document, and EN 1363-2 covers alternative and additional procedures <a href=\"https:\/\/webstore.uni.com\/en\/en-1363-2-1999\" target=\"_blank\" rel=\"noopener\">8<\/a>.<\/p>\n<h2>How the Furnace Is Controlled<\/h2>\n<h3>Temperature control<\/h3>\n<p>Getting the average furnace temperature to follow the curve is the engineering problem. It is done with an array of sheathed thermocouples whose tips project into the furnace space, a set of burners whose fuel and air are modulated continuously, and a controller that compares the measured average against the target curve several times a minute and trims the firing rate to close the gap.<\/p>\n<p>The thermocouple count and placement are specified by the standard rather than left to the manufacturer, and that matters because the &#8220;average furnace temperature&#8221; is literally the average of those readings. A probe that has drifted, or one that has been pushed back so its tip no longer projects into the furnace space, changes the number the controller is chasing and therefore changes the severity the specimen actually experiences. Routine verification of probe position and calibration is not optional maintenance; it is part of the test&#8217;s validity.<\/p>\n<h3>Pressure and exhaust<\/h3>\n<p>Two control variables matter beyond temperature itself. <strong>Furnace pressure<\/strong> matters because a furnace running at negative pressure draws cold laboratory air in and a furnace at excessive positive pressure leaks hot gas into the room; one furnace manufacturer&#8217;s description of the ISO 834-1 regime gives a positive pressure at the top of the furnace reaching 15 \u00b1 5 Pa within five minutes of the start and holding 17 \u00b1 3 Pa after ten minutes <a href=\"https:\/\/www.torontech.com\/zh-CN\/product\/horizontal-furnace\" target=\"_blank\" rel=\"noopener\">10<\/a>. <strong>Exhaust handling<\/strong> matters because the gas leaving the furnace is hot enough to damage ductwork, and a cooling stage before discharge is standard practice.<\/p>\n<h3>What an assessor will ask to see<\/h3>\n<p>The tolerances on how closely the measured average must track the target curve are set by the standard itself, and they are the first thing an accreditation assessor will ask to see documented. A laboratory should be able to produce a controller log showing measured versus target for the whole duration of every test, not just a pass statement. The same applies to the pressure record. In our experience the laboratories that struggle at assessment are not the ones with poor furnaces; they are the ones that never archived the trace.<\/p>\n<h2>The Three Criteria: R, E and I<\/h2>\n<figure style=\"margin:24px 0\">\n  <a href=\"https:\/\/brt-testing.com\/product\/vertical-integrated-fire-resistance-test-furnace\/\"><img decoding=\"async\" src=\"https:\/\/brt-testing.com\/wp-content\/uploads\/2026\/10\/fire-resistance-criteria-r-e-i.avif\" alt=\"Diagram of loadbearing capacity, integrity and insulation failure criteria in an ISO 834 fire resistance test\" width=\"1536\" height=\"864\" style=\"width:100%;height:auto\" loading=\"lazy\"><\/a><figcaption style=\"font-size:13px;color:#666;margin-top:6px\">The three independent criteria: loadbearing capacity R, integrity E, and insulation I. An element is rated to the time it holds all the criteria it is required to hold.<\/figcaption><\/figure>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:12.04%\">\n<col style=\"width:22.93%\">\n<col style=\"width:65.03%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Criterion<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">What it asks<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Failure is taken as<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><strong>R<\/strong> loadbearing capacity<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Does the element still carry its load?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">The element can no longer support the applied load; judged from deformation and rate of deformation<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><strong>E<\/strong> integrity<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Does the element still separate the two sides?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A cotton pad ignites on the unexposed face; a 6 mm gap gauge penetrates the specimen and can be moved 150 mm along a crack; a 25 mm gauge penetrates fully; flaming on the unexposed face persists longer than 10 s<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><strong>I<\/strong> insulation<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Does the element still stop heat passing through?<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">The mean temperature rise on the unexposed face exceeds 140 K above the initial mean, or the rise at any single point, including the moving thermocouple, exceeds 180 K<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>Two features of that table decide most disputes. The insulation criterion is <strong>dual<\/strong>: it is failed by an average, and it is also failed by any single point, so an element with a cold average and one hot spot fails on the point. And the three criteria are <strong>independent<\/strong>, so a loadbearing wall that loses insulation at 60 minutes but keeps carrying load at 120 minutes has a 60-minute I rating and a 120-minute R rating, and both have to be reported.<\/p>\n<p>The 140 K and 180 K figures are the conventional limits used across the European fire resistance methods, and EN 1363-1 is the document to cite for them [7].<\/p>\n<h3>Reading the insulation criterion in practice<\/h3>\n<p>The insulation criterion is the one that most often ends a test early, and it is the one most often misread. Because it is judged on both an average and a single point, the thermocouple layout on the unexposed face decides the outcome. A layout that misses a local hot area \u2014 a fixing point, a joint, a thinner section of the element \u2014 will report a comfortable average while the element is in fact conducting heat through that spot. This is why the standard specifies both fixed thermocouples at defined positions and a moving thermocouple used to search for the hottest region.<\/p>\n<p>The corollary is that the rating is specific to the element as built and as tested. Change the fixing centres, change the joint detail, or change the board thickness, and the insulation performance can move substantially without any change to the material. A report that states a rating without stating what was built is not a report that can be reused.<\/p>\n<figure style=\"margin:24px 0\">\n  <a href=\"https:\/\/brt-testing.com\/product\/horizontal-fire-resistance-test-furnace\/\"><img decoding=\"async\" src=\"https:\/\/brt-testing.com\/wp-content\/uploads\/2026\/10\/unexposed-face-thermocouple-layout.avif\" alt=\"Unexposed face thermocouple layout for the insulation criterion in an ISO 834 fire resistance test\" width=\"1536\" height=\"864\" style=\"width:100%;height:auto\" loading=\"lazy\"><\/a><figcaption style=\"font-size:13px;color:#666;margin-top:6px\">Thermocouple layout on the unexposed face. The average rise and the hottest single point are both judged, which is why a single hot spot can fail the element.<\/figcaption><\/figure>\n<h2>The ISO 834 Series: Which Part Applies<\/h2>\n<p>ISO 834-1 gives the <strong>general requirements<\/strong> [1]. The element-specific requirements sit in the later parts, and using Part 1 alone for a specific element type is a common error.<\/p>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:20.37%\">\n<col style=\"width:63.27%\">\n<col style=\"width:16.36%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Part<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Element covered<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Reference<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 834-1<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">General requirements<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">[1]<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 834-4<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Loadbearing vertical separating elements<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-4-2000\" target=\"_blank\" rel=\"noopener\">3<\/a><\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 834-5<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Loadbearing horizontal separating elements<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-5-2000\" target=\"_blank\" rel=\"noopener\">4<\/a><\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 834-8<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Non-loadbearing vertical separating elements<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-8-2002\" target=\"_blank\" rel=\"noopener\">5<\/a><\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 834-9<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Non-loadbearing ceiling elements<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-9-2003\" target=\"_blank\" rel=\"noopener\">6<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>A test programme for a loadbearing wall therefore cites Part 1 for the general apparatus and procedure and Part 4 for the element-specific requirements, and the report has to name both.<\/p>\n<h3>Why the edition change matters to a laboratory<\/h3>\n<p>ISO 834-1:1999 was the edition most laboratories built their procedures around, and it was withdrawn on 30 May 2025 [2]. ISO 834-1:2025 was published the same day [1]. For a working laboratory the practical task is a documentation one: find every place the 1999 edition is named \u2014 test procedures, report templates, quotation boilerplate, accreditation scope statements \u2014 and update the citation. The apparatus does not change because the edition changed, but a report citing a withdrawn standard is a report that will be queried.<\/p>\n<p>We have not verified clause-by-clause what the 2025 edition changed, and this article does not claim to. Where a procedure depends on a specific clause, tolerance or criterion, confirm it against the 2025 text rather than against an inherited procedure document.<\/p>\n<h2>Specifying and Buying a Furnace<\/h2>\n<p>ISO 834 fire resistance testing is a furnace-bound method, so the apparatus decision is really an element decision. The geometry of the furnace follows the element, and this is the first purchasing decision. A vertical furnace takes walls, doors and other vertical separating elements; a horizontal furnace takes floors, beams and horizontal elements. Laboratories that test both need both, and the horizontal furnace is the more demanding purchase because the element has to be loaded in a way that reproduces its real support conditions.<\/p>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:23.09%\">\n<col style=\"width:25.8%\">\n<col style=\"width:29.34%\">\n<col style=\"width:21.77%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Requirement<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">BRT apparatus<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Product page<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Note<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Walls, doors and vertical separating elements<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Vertical Integrated Fire Resistance Test Furnace<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"\/product\/vertical-integrated-fire-resistance-test-furnace\/\">\/product\/vertical-integrated-fire-resistance-test-furnace\/<\/a><\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 834-1 with the vertical element parts<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Floors, beams and horizontal elements<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Horizontal Fire Resistance Test Furnace<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"\/product\/horizontal-fire-resistance-test-furnace\/\">\/product\/horizontal-fire-resistance-test-furnace\/<\/a><\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">ISO 834-5 and related parts<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Coated steel sections<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Steel Fire Retardant Coating Test Furnace<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"\/product\/steel-fire-retardant-coating-test-furnace\/\">\/product\/steel-fire-retardant-coating-test-furnace\/<\/a><\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">For intumescent coating assessment<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Full range<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Fire &amp; Flame Testing Equipment<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\"><a href=\"\/fire-flame-testing-equipment\/\">\/fire-flame-testing-equipment\/<\/a><\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Category page<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<p>For the wider context of how a fire resistance test is run end to end, see <a href=\"\/how-fire-resistance-is-tested-for-building-materials\/\">how fire resistance is tested for building materials<\/a>; for steel specifically, see <a href=\"\/fire-resistance-testing-for-steel-structures-key-requirements\/\">fire resistance testing for steel structures<\/a>.<\/p>\n<h2>Common Mistakes<\/h2>\n<div class=\"brt-table-wrap\" style=\"overflow-x:auto;margin:1.5em 0;-webkit-overflow-scrolling:touch\">\n<table style=\"border-collapse:collapse;width:100%;table-layout:auto\">\n<colgroup>\n<col style=\"width:32.03%\">\n<col style=\"width:36.53%\">\n<col style=\"width:31.44%\"><\/colgroup>\n<thead>\n<tr>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Mistake<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Consequence<\/th>\n<th style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word;background:#f2f4f7;font-weight:600\">Fix<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Citing ISO 834-1:1999<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">The edition was withdrawn on 30 May 2025<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Cite ISO 834-1:2025<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Using Part 1 without the element-specific part<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Element-specific requirements missed<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Name ISO 834-1 plus the relevant part on the report<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Treating an ISO 834 hour as an ASTM E119 hour<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Two different curves, not interchangeable<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Name the standard on every rating<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Reading the insulation criterion as an average only<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">A single hot spot is missed and the element is wrongly passed<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Judge average and hottest single point<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Reporting a single rating for R, E and I<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">The element&#8217;s real performance is misrepresented<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Report each required criterion separately<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">No controller log of measured versus target<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Accreditation assessor cannot verify curve tracking<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Retain the log for the whole duration<\/td>\n<\/tr>\n<tr>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Ignoring furnace pressure control<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Cold air ingress, or hot gas leaking into the room<\/td>\n<td style=\"border:1px solid #c9ced6;padding:9px 11px;vertical-align:top;overflow-wrap:break-word\">Control and record pressure from the start<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<\/div>\n<h2>Frequently Asked Questions<\/h2>\n<h4>What is the equation for the ISO 834 temperature-time curve?<\/h4>\n<p>T = 20 + 345 log\u2081\u2080(8t + 1), where T is the average furnace temperature in degrees Celsius and t is the elapsed time in minutes from the start of the test. It gives roughly 842 \u00b0C at 30 minutes, 945 \u00b0C at 60 minutes, 1,006 \u00b0C at 90 minutes and 1,049 \u00b0C at 120 minutes.<\/p>\n<h4>Is ISO 834 the same as ASTM E119?<\/h4>\n<p>No. ISO 834 specifies the curve as a single equation, while ASTM E119 specifies a tabulated set of temperature-time points. The two curves are close but not identical, with the largest differences in the first ten minutes, so a rating of one hour under one standard is not interchangeable with an hour under the other.<\/p>\n<h4>What do R, E and I mean in a fire resistance rating?<\/h4>\n<p>They are three independent criteria. R is loadbearing capacity, whether the element still carries its applied load. E is integrity, whether it still separates the two sides against flame and hot gas. I is insulation, whether it still limits heat passing through. An element is rated to the time it holds every criterion it is required to hold, and each is reported separately.<\/p>\n<h4>What temperature rise fails the insulation criterion?<\/h4>\n<p>The insulation criterion is failed when the mean temperature rise on the unexposed face exceeds 140 K above the initial mean temperature, or when the rise at any single point, including the moving thermocouple, exceeds 180 K. Because both the average and the hottest single point are judged, one local hot spot can fail the element even when the average looks acceptable.<\/p>\n<h4>Which edition of ISO 834-1 is current?<\/h4>\n<p>ISO 834-1:2025, published on 30 May 2025, is the current edition. ISO 834-1:1999 was withdrawn on the same day. Test plans and reports still citing the 1999 edition should be updated before they are signed off.<\/p>\n<h4>Do I need a vertical or a horizontal furnace?<\/h4>\n<p>It depends on the element. Vertical furnaces take walls, doors and other vertical separating elements; horizontal furnaces take floors, beams and horizontal elements. A laboratory that tests both categories needs both, because the horizontal furnace also has to reproduce the element&#8217;s real support conditions.<\/p>\n<h4>Why does the curve flatten out after the first hour?<\/h4>\n<p>Because the equation is logarithmic, so each additional minute adds less temperature than the one before. The curve gains roughly 270 \u00b0C in the first five minutes but only about 100 \u00b0C between two and four hours, which means the severity is heavily front-loaded and later failures are driven by the element&#8217;s slow thermal response.<\/p>\n<h2>Conclusion: How to Decide<\/h2>\n<ol>\n<li>Confirm the edition \u2014 ISO 834-1:2025 is current and the 1999 edition was withdrawn on 30 May 2025.<\/li>\n<li>Identify the element type and name the right part of the series alongside Part 1.<\/li>\n<li>Decide which of R, E and I the element is required to hold, and report each separately rather than as one number.<\/li>\n<li>Choose furnace geometry from the element: vertical for walls and doors, horizontal for floors and beams.<\/li>\n<li>Require a controller log of measured versus target temperature, and a pressure record, for the full duration of every test.<\/li>\n<li>If the product is sold into North America as well, plan a separate ASTM E119 programme rather than assuming the ISO rating carries over.<\/li>\n<\/ol>\n<p>BRT builds vertical and horizontal fire resistance test furnaces configured to the ISO 834 series. Send us the element types you need to test and the ratings you are targeting, and we will map that to a furnace, a control system and an installation plan. Start from the <a href=\"\/fire-flame-testing-equipment\/\">fire and flame testing equipment range<\/a>, or read <a href=\"\/how-to-choose-a-fire-testing-laboratory-equipment-supplier\/\">how to choose a fire testing laboratory equipment supplier<\/a> if you are at the supplier-selection stage.<\/p>\n<p><strong>About the author.<\/strong> This article was prepared by the BRT combustion testing application team at Shenyang Baoruitong Automation Equipment, which manufactures fire testing and laboratory instrumentation for construction product, steel, transport and plastics laboratories. Edition dates and withdrawal dates were checked against ISO, CEN and ASTM catalogue entries on the dates given below. Curve values were computed from the equation in ISO 834-1.<\/p>\n<h2>Sources<\/h2>\n<ol>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-1-2025\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 ISO 834-1:2025<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-1-1999\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 ISO 834-1:1999<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-4-2000\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 ISO 834-4:2000<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-5-2000\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 ISO 834-5:2000<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-8-2002\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 ISO 834-8:2002<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/iso-834-9-2003\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 ISO 834-9:2003<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/en-1363-1-2020\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 EN 1363-1:2020<\/a><\/li>\n<li><a href=\"https:\/\/webstore.uni.com\/en\/en-1363-2-1999\" target=\"_blank\" rel=\"noopener\">UNI Ente Italiano di Normazione \u2014 EN 1363-2:1999<\/a><\/li>\n<li><a href=\"https:\/\/store.astm.org\/e0119-24.html\" target=\"_blank\" rel=\"noopener\">ASTM International \u2014 E119-24 Standard Test Methods for Fire Tests of Building Construction and Materials<\/a><\/li>\n<li><a href=\"https:\/\/www.torontech.com\/zh-CN\/product\/horizontal-furnace\" target=\"_blank\" rel=\"noopener\">Torontech \u2014 Horizontal fire resistance furnace (manufacturer technical page)<\/a><\/li>\n<\/ol>\n<p><!-- FAQ \/ Article JSON-LD --><br \/>\n<script type=\"application\/ld+json\">\n{\n  \"@context\": \"https:\/\/schema.org\",\n  \"@type\": \"FAQPage\",\n  \"mainEntity\": [\n    {\n      \"@type\": \"Question\",\n      \"name\": \"What is the equation for the ISO 834 temperature-time curve?\",\n      \"acceptedAnswer\": {\n        \"@type\": \"Answer\",\n        \"text\": \"T = 20 + 345 log\u2081\u2080(8t + 1), where T is the average furnace temperature in degrees Celsius and t is the elapsed time in minutes from the start of the test. It gives roughly 842 \u00b0C at 30 minutes, 945 \u00b0C at 60 minutes, 1,006 \u00b0C at 90 minutes and 1,049 \u00b0C at 120 minutes.\"\n      }\n    },\n    {\n      \"@type\": \"Question\",\n      \"name\": \"Is ISO 834 the same as ASTM E119?\",\n      \"acceptedAnswer\": {\n        \"@type\": \"Answer\",\n        \"text\": \"No. ISO 834 specifies the curve as a single equation, while ASTM E119 specifies a tabulated set of temperature-time points. The two curves are close but not identical, with the largest differences in the first ten minutes, so a rating of one hour under one standard is not interchangeable with an hour under the other.\"\n      }\n    },\n    {\n      \"@type\": \"Question\",\n      \"name\": \"What do R, E and I mean in a fire resistance rating?\",\n      \"acceptedAnswer\": {\n        \"@type\": \"Answer\",\n        \"text\": \"They are three independent criteria. R is loadbearing capacity, whether the element still carries its applied load. E is integrity, whether it still separates the two sides against flame and hot gas. I is insulation, whether it still limits heat passing through. An element is rated to the time it holds every criterion it is required to hold, and each is reported separately.\"\n      }\n    },\n    {\n      \"@type\": \"Question\",\n      \"name\": \"What temperature rise fails the insulation criterion?\",\n      \"acceptedAnswer\": {\n        \"@type\": \"Answer\",\n        \"text\": \"The insulation criterion is failed when the mean temperature rise on the unexposed face exceeds 140 K above the initial mean temperature, or when the rise at any single point, including the moving thermocouple, exceeds 180 K. Because both the average and the hottest single point are judged, one local hot spot can fail the element even when the average looks acceptable.\"\n      }\n    },\n    {\n      \"@type\": \"Question\",\n      \"name\": \"Which edition of ISO 834-1 is current?\",\n      \"acceptedAnswer\": {\n        \"@type\": \"Answer\",\n        \"text\": \"ISO 834-1:2025, published on 30 May 2025, is the current edition. ISO 834-1:1999 was withdrawn on the same day. Test plans and reports still citing the 1999 edition should be updated before they are signed off.\"\n      }\n    },\n    {\n      \"@type\": \"Question\",\n      \"name\": \"Do I need a vertical or a horizontal furnace?\",\n      \"acceptedAnswer\": {\n        \"@type\": \"Answer\",\n        \"text\": \"It depends on the element. Vertical furnaces take walls, doors and other vertical separating elements; horizontal furnaces take floors, beams and horizontal elements. A laboratory that tests both categories needs both, because the horizontal furnace also has to reproduce the element's real support conditions.\"\n      }\n    },\n    {\n      \"@type\": \"Question\",\n      \"name\": \"Why does the curve flatten out after the first hour?\",\n      \"acceptedAnswer\": {\n        \"@type\": \"Answer\",\n        \"text\": \"Because the equation is logarithmic, so each additional minute adds less temperature than the one before. The curve gains roughly 270 \u00b0C in the first five minutes but only about 100 \u00b0C between two and four hours, which means the severity is heavily front-loaded and later failures are driven by the element's slow thermal response.\"\n      }\n    }\n  ]\n}\n<\/script><\/p>\n","protected":false},"excerpt":{"rendered":"<p>ISO 834 fire resistance testing exposes a building element to a single standardised temperature-time curve, T = 20 + 345 log10(8t + 1), and measures how long the element survives before failing loadbearing capacity, integrity or insulation. This article computes the curve at ten time points, explains why it is a convention rather than a physical law, sets out how the furnace is controlled and why pressure matters, details the R, E and I criteria and why insulation is judged on both an average and a single hot spot, and maps the ISO 834 parts to the element types they cover.<\/p>","protected":false},"author":1,"featured_media":1556,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[135],"tags":[],"class_list":["post-1616","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-interpretation-of-the-standard"],"_links":{"self":[{"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/posts\/1616","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/comments?post=1616"}],"version-history":[{"count":2,"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/posts\/1616\/revisions"}],"predecessor-version":[{"id":1677,"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/posts\/1616\/revisions\/1677"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/media\/1556"}],"wp:attachment":[{"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/media?parent=1616"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/categories?post=1616"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/brt-testing.com\/it\/wp-json\/wp\/v2\/tags?post=1616"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}