JCKR Building Material Combustibility Test Apparatus strictly complies with ISO 11925-2:2026, EN 13501-1 (Euroclass B/C/D/E), GB/T 8626, DIN 4102-1 (B2), and EN 13238 standards. Features a 1.5mm stainless steel cabinet, 7-inch industrial touchscreen, motorized burner 45° positioning, high-voltage auto-ignition with 5s/15s/30s timers, and a complete mounting accessory kit for Class B1/B2 fire classification.

SKU: JCKR, Categories: ,
Inquiry Now

EMAIL ADDRESS

FIRST NAME

LAST NAME

whatsapp

MESSAGE

The JCKR Building Material Combustibility Test Apparatus is a high-precision, professional single-flame fire testing instrument developed strictly in accordance with ISO 11925-2:2026, EN 13501-1 (Euroclass B/C/D/E), GB/T 8626, DIN 4102-1 (B2), and EN 13238 standards. It is engineered to perform vertical single-flame impingement tests on flat construction and decorative material samples without external thermal radiation, assessing direct ignitability and flame spread behavior.

Essential for classifying building materials into fire resistance grades B1 (flame retardant) and B2 (combustible) as required by GB 8624, as well as European Euroclass grades, this versatile Single Flame Ignitability Tester features a 1.5mm heavy-duty stainless steel cabinet, a 7-inch industrial color touchscreen, full motorized mechanical adjustment (for burner 45° tilting and specimen positioning), high-voltage auto-ignition, and a complete suite of standard mounting accessories for certified quality inspection and product R&D.


Building Material Combustibility Test Apparatus Compliance & Standards

This single flame ignitability tester allows certified laboratories to execute formal reaction-to-fire tests across global building material, railway, and marine classification frameworks:

Standard Code Standard Title & Scope Primary Testing Application
ISO 11925-2:2026 / BS EN ISO 11925-2 Reaction to fire tests — Ignitability of products subjected to direct impingement of flame — Part 2: Single-flame source test International benchmark for direct single-flame surface and edge ignitability testing
EN 13501-1 Fire classification of construction products and building elements — Reaction to fire classification Mandatory European classification testing for Euroclass B, C, D, and E building products
DIN 4102-1 (Class B2) Fire behaviour of building materials and building components — Part 1: Building materials requirements German national fire classification standard for normal flammability (B2 grade) testing
DIN 5510-2 / TB/T 3237 Preventive fire protection in railway vehicles — Flammability & flame spread of non-metallic components German and Chinese railway safety compliance for train interior decorative materials and plastics
GB/T 8626 & GB 8624 Test Method for Combustibility of Building Materials & Fire Classification Assessment Mandatory Chinese national standards for Class B1 and B2 building product fire safety evaluations
EN 13238 Reaction to fire tests for building products — Conditioning procedures and general rules for selection of substrates Specimen conditioning and standardized mounting rules for European Euroclass testing

Technological Features of JCKR Single Flame Ignitability Tester

  • Full Stainless Steel Enclosure with Double Tempered Glass Windows: Constructed with a 1.5mm thick corrosion-resistant stainless steel cabinet designed for rigorous daily laboratory use. Dual heat-resistant tempered glass doors provide multi-angle visual tracking without compromising chamber airflow or operator safety.
  • Full Electric Motorized Positioning & Automated 45° Burner Tilt: Features motor-driven vertical sample lifting and electric 45° tilting/reset for the burner assembly. The burner adjusts forward, backward, left, and right to perfectly match diverse specimen thicknesses, including melting or multi-layer materials.
  • 7-Inch Industrial Touchscreen Controller with Built-in 4G Storage: Driven by an industrial color touch panel (800×480 resolution) with 512M RAM and 4GB built-in storage. Offers one-touch parameter setups, configurable flame exposure timers (5s / 15s / 30s), automatic curve logging, and USB data export.
  • High-Voltage Auto-Ignition & Retractable Flame System: Equipped with a high-voltage electronic ignition system with auto-reset capabilities. The burner automatically advances to the specimen for the programmed duration (e.g., 15s or 30s) and retracts upon test completion to ensure repeatable flame application.
  • All-Inclusive Standard Accessory Kit Included: Supplied with 3 specialized specimen holder types (for standard, melting/shrinking, and thick multi-layer samples >10mm), a 90° rotating hanging bracket, specimen preparation molds, dual burner gauges, and an adjustable exhaust fan with an air velocity sensor.

Technical Specifications of Building Material Combustibility Test Apparatus

Governing Test Standards ISO 11925-2:2020, BS EN ISO 11925-2, EN 13501-1, DIN 4102-1 (B2), DIN 5510-2, GB/T 8626, GB 8624, EN 13238, TB/T 3237
Cabinet Construction & Material 1.5 mm thick 304 Stainless Steel plate; double tempered view windows
Burner Inclination & Movement Fixed 45° inclination angle; motorized electric advance, retraction, and 3-axis alignment
Ignition & Flame Exposure Timer High-voltage electronic auto-ignition; 5s / 15s / 30s programmable auto-switch
Display & Storage Architecture 7-inch industrial touchscreen (800×480); 512M RAM / 4G storage; USB export
Test Fuel & Gas Pressure Commercial Propane (purity ≥ 95%); Supply Pressure: 10 kPa to 50 kPa
Exhaust & Air Velocity Sensing Integrated speed-adjustable exhaust fan with inline anemometer sensor
Specimen Support & Height Motorized vertical height adjustment; support height fixed at 40 mm
Operating Environment & Power 18°C–28°C; 30%–70% RH; AC 220V ±5%, 50 Hz; Total Power: 500 W

System Architecture & Testing Workflow of Single Flame Ignitability Tester

Standardized Testing Workflow:

  1. Mount the flat specimen (or multi-layer board) into the appropriate stainless steel specimen frame.
  2. Position the burner and set the flame height to 20mm using the included flame calibration gauge.
  3. Select the surface or edge impingement mode and preset the flame application time (e.g., 15s or 30s) on the 7-inch touchscreen.
  4. Initiate the auto-ignition sequence; the burner automatically tilts to 45°, advances to the specimen, applies the flame, and retracts precisely when the timer expires.
  5. Observe whether the flame tip reaches the 150mm mark on the sample within the specified time, then log the archived test report on the PC or USB drive.

Target Customer Applications:

  • Flat wall panel, insulation board, flooring, and decorative composite product factories.
  • Third-party fire safety testing laboratories and international material certification bodies.
  • Construction engineering inspection bureaus and architectural quality supervision departments.
  • University material engineering departments and fire safety science research centers.

Building Material Combustibility Test Apparatus FAQ

Q1: What is the difference between Surface Impingement and Edge Impingement in ISO 11925-2?

A: Surface impingement applies the 45° flame directly onto the flat face of the specimen (typically 40mm above the bottom edge). Edge impingement applies the flame directly to the center of the bottom edge of the sample. The JCKR tester easily toggles between both modes using motorized adjustments.

Q2: What role does ISO 11925-2 play in the European Euroclass fire classification system?

A: ISO 11925-2 is a mandatory reaction-to-fire test required for Euroclass B, C, D, and E classifications under EN 13501-1. Passing this single-flame test proves that a material resists small flame ignition without rapid flame spread.

Q3: Are additional mounting accessories required for testing thick or melting materials?

A: No. The JCKR apparatus comes complete with 3 standard sample holder configurations, including multi-layer frames for specimens over 10mm thick and specialized grid trays for materials that melt or shrink away from the flame.

Test Parameter

Ignitability

Standard

EN 13238, GB 8624, GB/T 40238, GB/T 8626, ISO 11925-2:2020

Reviews

There are no reviews yet.

Be the first to review “JCKR Building Material Combustibility Test Apparatus for SINGLE FLAME SOURCE TESTING”

Your email address will not be published. Required fields are marked *