NH-XL Vertical Integrated Fire Resistance Test Furnace strictly complies with GB/T 9978, GB 12955-2024, GB 16809-2024, و ايزو 834-1 المعايير. Features a 3.0m × 3.0m × 1.2m cavity, lightweight high-alumina zirconia fiber suspended lining (up to 1300°C), 8 proportional gas burners, closed-loop pressure control, and automated PC data logging for fire doors, windows, shutters, and partition wall integrity & insulation testing.

رمز التخزين التعريفي: NH-XL, فئات: ,
الاستفسار الآن

عنوان البريد الإلكتروني

الاسم الأول

اسم العائلة

واتس اب

رسالة

ال NH-XL Vertical Integrated Fire Resistance Test Furnace (Vertical Comprehensive Fire-Resistance Test Furnace) is a full-scale, automated laboratory testing system engineered to evaluate the fire-resistance limit, thermal insulation performance, and structural integrity of vertical fire-partition walls, doors, windows, glass, roller shutters, and check valves/non-return valves. It strictly complies with ايزو 834-1/4/8, في 1363-1, في 1634-1, BS 476 (Parts 20/22), ASTM E119, أول 263, and mandatory national standards جيجابايت/ت 9978 و GB 12955-2024.

Built with a robust enamel-coated steel outer shell, lightweight high-alumina fiber suspended furnace body, zirconium-fiber block insulation capable of withstanding up to 1300°C, an 8-burner proportional gas combustion array, and automatic closed-loop pressure/temperature control, this heavy-duty Fire Resistance Testing Furnace provides authoritative compliance data for building material manufacturers, third-party fire testing laboratories, marine classification societies, and construction quality inspection bureaus.


Vertical Comprehensive Fire-Resistance Test Furnace Compliance & المعايير

This vertical fire resistance testing furnace allows certified laboratories to perform formal fire limit assessments across global building, marine, and door/window safety standards:

الكود القياسي العنوان القياسي & نِطَاق تطبيق الاختبار الأساسي
ايزو 834-1 / 4 / 8 & BS 476-20/22 Fire-resistance tests for elements of building construction — General requirements & vertical separating elements International benchmark for standard time-temperature fire curve compliance and vertical partition testing
في 1363-1 & في 1634-1/3 Fire resistance tests — General requirements & Fire resistance test for door, shutter assemblies and openable windows European CE/CPR qualification testing for fire doors, shutters, window assemblies, and non-return valves
ASTM E119 & أول 263 Standard Test Methods for Fire Tests of Building Construction and Materials North American vertical partition wall and structural element fire endurance testing
GB/T 9978.1~4 & GB 12955-2024 Fire-resistance tests for building construction elements & Fire doors mandatory specification Mandatory Chinese national standard for fire doors, shutters, partition panels, and check/non-return valves
IMO FTP Code Part 3 International Code for Application of Fire Test Procedures — Test for “أ”, “B” و “F” Class Divisions Marine fire safety compliance for shipboard vertical bulkheads, fire doors, and exhaust dampers

Technological Features of H-XL Fire Resistance Test Furnace

  • Advanced Thermal Lining & High-Temperature Resistance: Constructed with a baked-enamel steel outer casing and a lightweight high-alumina fiber suspended roof lined with zirconium-fiber wool block modules, ensuring minimal heat loss up to a maximum operating temperature of 1300°C.
  • 8-Burner Proportional Gas Combustion System: Fueled by Natural Gas or LPG, the 8-burner array delivers uniform open-flame heating controlled via programmed temperature-rise software according to the standard curve: $T – T_0 = 345 \lg (8t + 1)$.
  • Automated Closed-Loop Furnace Pressure Control: Precision pressure sensors located 100mm from the specimen surface dynamically adjust exhaust dampers to maintain constant furnace pressure (15 ± 5 Pa at 5 min, 17 ± 3 Pa at 10 min).
  • Computer-Aided Management & Multi-Channel Thermal Monitoring: Fully automated program-driven operation logs real-time unexposed face temperature rises (monitoring mean 140°C and single-point 180°C insulation limits) and structural integrity loss.
  • External Specimen Mounting & Rear Exhaust Integration: External specimen fixing layout facilitates rapid loading and unloading of 3m × 3m test frames. The rear mechanical smoke exhaust connects directly to facility dust-removal and scrub systems.

Technical Specifications of Vertical Comprehensive Fire-Resistance Test Furnace

معايير الاختبار الحاكمة ايزو 834-1/4/8, في 1363-1, في 1634-1/3, BS 476-20/22, ASTM E119, أول 263, IMO FTP Part 3, جيجابايت/ت 9978, GB 12955-2024
Internal Furnace Chamber Dimensions 3.0 m (W) × 3.0 m (H) × 1.2 m (D)
Overall Equipment Dimensions 8,000 مم (L) × 6,000 مم (W) × 7,000 مم (H) (Net height: 5,500 مم)
Fuel & Burner System Natural Gas or Liquefied Petroleum Gas (LPG); 8 proportional burners
Maximum Operating Temperature 1300درجة مئوية
Furnace Pressure Control 5 min: 15 Pa ± 5 Pa; 10 min: 17 Pa ± 3 Pa (Measured 100 mm from specimen)
Thermal Insulation Criteria Mean unexposed surface temp rise > 140درجة مئوية, or single-point temp rise > 180درجة مئوية
Structural Insulation Material High-alumina fiber suspended roof & zirconium-fiber wool block-module lining
Combustion & Exhaust Control Automatic curve tracking, proportional gas regulation, computer management, rear mechanical exhaust

System Architecture & Testing Workflow of H-XL Fire Resistance Test Furnace

سير عمل الاختبار الموحد:

  1. Mount the vertical specimen (fire door, window, glass partition, roller shutter, or non-return valve) onto the 3m × 3m test frame and position it at the furnace front.
  2. Attach unexposed face thermocouples to record surface temperature rise and integrity monitoring instruments.
  3. Initialize the automated program on the PC interface and trigger the 8 gas burners.
  4. The proportional control system adjusts fuel and air supply to track the standard time-temperature curve $T – T_0 = 345 \lg (8t + 1)$ while maintaining furnace pressure at 15–17 Pa.
  5. Monitor specimen integrity and insulation failure; upon test termination, automatically extinguish burners, archive test data, and activate rear mechanical smoke exhaust.

تطبيقات العملاء المستهدفة:

  • Fire doors, fire windows, glass curtains, and roller shutter manufacturers.
  • HVAC check valves, oil-fume exhaust non-return valves, and fire damper production lines.
  • Third-party fire protection product inspection bureaus and international certification bodies.
  • Civil engineering, architectural safety, and fire research institutes.

H-XL Vertical Comprehensive Fire-Resistance Test Furnace FAQ

س1: What types of specimens can be evaluated using this vertical test furnace?

أ: The H-XL furnace evaluates non-loadbearing and loadbearing vertical separating elements, including fire doors, fire windows, fireproof glass partitions, roller shutters, hollow wall panels, and ventilation/oil-fume exhaust check (non-return) valves.

Q2: How does the furnace control pressure according to GB/T 9978 and EN 1363?

أ: Pressure sensors continuously measure furnace pressure at a 3m height, 100mm from the specimen. The automated PLC system dynamically adjusts the rear mechanical exhaust damper to maintain 15 ± 5 Pa at 5 minutes and 17 ± 3 Pa at 10 minutes.

س3: What indicates a loss of thermal insulation during testing?

أ: Loss of thermal insulation is recorded when either the average temperature rise on the unexposed face of the specimen exceeds 140°C above the initial temperature, or the temperature rise at any single measurement point exceeds 180°C above its initial value.

Test Parameter

Flame Spread

معيار

BS 476, في 1363-1, GB 12955-2024, GB 16809-2024, جيجابايت/ت 23449, جيجابايت/ت 23450, جيجابايت/ت 23451, جيجابايت/ت 38252-2019, جيجابايت/ت 7633, جيجابايت/ت 9978.1, جيجابايت/ت 9978.2, جيجابايت/ت 9978.4, جيجابايت/ت 9978.8, ايزو 834

التعليقات

لا توجد تعليقات حتى الآن.

كن أول من يقيم “NH-XL Vertical Integrated Fire Resistance Test Furnace”

لن يتم نشر عنوان بريدك الإلكتروني. تم وضع علامة على الحقول المطلوبة *